this post was submitted on 16 Jun 2025
291 points (92.9% liked)
Technology
71558 readers
4385 users here now
This is a most excellent place for technology news and articles.
Our Rules
- Follow the lemmy.world rules.
- Only tech related news or articles.
- Be excellent to each other!
- Mod approved content bots can post up to 10 articles per day.
- Threads asking for personal tech support may be deleted.
- Politics threads may be removed.
- No memes allowed as posts, OK to post as comments.
- Only approved bots from the list below, this includes using AI responses and summaries. To ask if your bot can be added please contact a mod.
- Check for duplicates before posting, duplicates may be removed
- Accounts 7 days and younger will have their posts automatically removed.
Approved Bots
founded 2 years ago
MODERATORS
you are viewing a single comment's thread
view the rest of the comments
view the rest of the comments
#1 is a terrible idea if you ever need to hire an electrician in the future, plan on selling your house, etc. The National Electric Code prohibits using white, green, or grey wire for a hot/load connection. The 120V cable will contain a black wire for the hot connection, white for neutral, and green for ground. To properly convert it to 240V you would need a cable that consists of black & red wires for the two 120V legs.
If your home ever suffered an electrical fire then this sort of jury rigging is precisely the sort of thing any competent insurance inspector would spot, and insurance carriers would deny coverage for since it clearly isn’t code compliant, which means a licensed electrician didn’t install it and it wasn’t properly inspected.
I'll be the first to admit I'm no certified Sparky, but wire relabeling is used in a number of situations fully in accordance with NEC. My understanding is that some of this is in NEC 200.7. It requires relabeling both ends, but I don't think there's any code violation with it. If what you're saying was true, wouldn't that mean any -2 NM (Romex) would be code incompatible with 240v loads? I don't think that's true.
Edit: here's a Sparky doing exactly that
The "120 volt cable", assuming you mean NM-B aka Romex, is rated for up to 600 volts if you look at it closely. It is absolutely acceptable to use that wiring for a 240V circuit, as long as you wrap colored (not green) electrical tape around the white neutral wire to indicate it's another hot.
Yes, there are 3-conductor (plus ground) wires one can also use for switches and 240V circuits with neutral. That neutral can be used to have 120V and 240V together (your oven may use 240V coils, but the light bulb probably runs on 120). Doesn't mean you need to have it, if your 240V circuit doesn't need a neutral. My air compressor is just a motor that can run at 240, no neutral needed, and its outlet is wired up with the same kind of Romex used for a 120 right next to it (with black tape to indicate a second hot)